They are
cheap, even if strong, filtering cells at medium efficiency, composed of a
self extinguishing (F1class according to DIN 53438) synthetic filtering
media, kept by two zinc-plated wire nets (mesh 12x24 mm) and boxed into a
5/10 mm galvanized steel frame. |
|
APPLICATIONS
|
They are
used for fan-coil, air treatment units, warm air generators, ventilation
equipement of machines and as prefilters to filters having higher
performances (like LOM-BAG pockets filters, rigid pockets or activated carbon
filters). |
FEATURES |
The
filtration classes of these filters, according to EN 779 Standards, are G 3
for filters with 23 and 48 mm thickness and G 2 for filters having 12 mm
thickness. See the
Table. |
INSTALLATION & SERVICE |
The CK filters can be installed into
C-shaped guides or into holding frames at frontal access. Replace or
regenerate the cells once having reached a resistance of 200 Pa. Clean by
shaking (in case of rough and dry dust) or by counter current air or by warm
water and cleaning agent. |